Antifreeze performance laboratory of gas heating furnace
The antifreeze performance laboratory of gas heating furnaces is to test the freezing resistance performance of heating furnaces in windy conditions. Adjust the temperature in the test chamber to -10℃±2℃, and blow it to the heating furnace with a wind speed of 3m/s to test its antifreeze performance. This antifreeze performance laboratory meets the GB 25034-2020 standard.
- Product Details
Meet the standard: GB 25034-2020
Test Methods:
1. Blow air for 4 hours in the standby state. During the test, the temperature outside the room should be kept constant to ensure that the indoor thermostat will not start the heating furnace, and then test the water temperature of heating water, domestic hot water and condensed water.
2. In the heating state, run for 0.5h under the minimum heat load, and test the water temperature of heating water, domestic hot water and condensate water.
3. In the state of domestic hot water, run for 0.5h under the minimum heat load, and test the temperature of heating water, domestic hot water and condensate water.
Product schematic diagram of antifreeze performance laboratory of gas heating furnace: