Air volume test bench for air outlet of purifier
Product Usage:
The Air volume test bench for air outlet of purifier uses the method of "
constant static pressure" to measure relevant parameters and air volume.
Set static pressure value: When the test fan is running, the current static
pressure value changes, the PID instrument reads the current static pressure
value through the sensor, and compares it with the set static pressure value.
If the current static pressure value does not reach the set static pressure value,
the PID instrument automatically adjusts the speed of the auxiliary fan and controls
the air volume of the auxiliary fan so that the current static pressure value reaches
the set static pressure value. When the static pressure value is stable, measure the
relevant parameters required to calculate the air volume, and calculate the air volume
of the test fan.
- Product Details
Fulfill the standard:
GB/T1236-2000
Performance Test of Standardized Air Duct for Industrial Ventilators
GB/T2624.3-2006
Uses the differential pressure device installed in the circular surface pipeline to measure the fluid flow of the full pipe
Standard parameters:
Index parameter
Range
Accuracy
Control1)
Air volume(m3/h)
50~2000
≤±3%2)
Static pressure(Pa)
0~1000
±0.5%
Note: 1) Control parameters.
Measurement
Temperature(℃)
0~50
±1
Humidity(%RH)
10~99%
±2%
Atmospheric pressure(A.kPa)
80~110
±0.5%
Nozzle differential pressure(Pa)
0~1000
±2%
2) The air volume measurement accuracy is ±3% of the actual measurement value.